# SUN-5/6/8/10/12K-SG04LP3 and SUN-5/6/8/10/12/15/20/25K-SG01HP3-EU-AM2 | 5-32kW and 5-128kW | Three Phase | 4 MPPT | Hybrid Inverter | LV and HV Battery Supported
#
# Reference: https://github.com/user-attachments/files/16798469/MODBUS.RTU.V105.1-20231006.pdf and https://github.com/user-attachments/files/16597916/MODBUSRTU.V104.3.1.1111_SG01-HP3-AM2.pdf
#
# Tested with 25K-SG01HP3 12K-SG04LP3 and LSW3_15_FFFF_1.0.91R Stick Logger
#
info:
manufacturer: Deye
model: [SG0*LP3, SG0*HP3]
default:
update_interval: 60
digits: 6
parameters:
- group: Info
update_interval: 3600
items:
- name: "Device"
class: "enum"
rule: 1
registers: [0x0000]
icon: "mdi:information"
lookup:
- key: 0x0000
value: "Unknown"
- key: [0x0002, 0x0200]
value: "String Inverter"
- key: [0x0003, 0x0300]
value: "Single-Phase Hybrid Inverter"
- key: [0x0004, 0x0400]
value: "Microinverter"
- key: [0x0005, 0x0500]
value: "LV 3-Phase Hybrid Inverter"
- key: 0x0006
value: "HV 3-Phase Hybrid Inverter"
- key: [0x0007, 0x0600]
value: "HV 3-Phase Inverter 6-15kw"
- key: [0x0008, 0x0601]
value: "HV 3-Phase Inverter 20-50kw"
attributes:
[
"Device Modbus Address",
"Device Protocol Version",
"Device Serial Number",
"Device Control Board Firmware Version",
"Device Communication Board Firmware Version",
"Device MCU Board Version",
"Device MCU Version",
"Device AFCI Version",
"Device Rated Power",
"Device MPPTs",
"Device Phases",
]
- name: "Device Modbus Address"
attribute:
rule: 1
registers: [0x0001]
- name: "Device Protocol Version"
attribute:
rule: 7
remove: "0."
registers: [0x0002]
- name: "Device Serial Number"
attribute:
rule: 5
registers: [0x0003, 0x0004, 0x0005, 0x0006, 0x0007]
- name: "Device MCU Board Version"
attribute:
rule: 7
delimiter: ""
registers: [0x000A]
- name: "Device AFCI Version"
attribute:
rule: 7
delimiter: ""
registers: [0x000C]
- name: "Device MCU Version"
attribute:
rule: 7
delimiter: ""
registers: [0x000D]
- name: "Device Control Board Firmware Version"
attribute:
rule: 7
delimiter: ""
registers: [0x000E, 0x000F, 0x000B]
- name: "Device Communication Board Firmware Version"
attribute:
rule: 7
hex:
delimiter: ""
registers: [0x0011, 0x0012, 0x0010]
- name: "Device Rated Power"
attribute:
class: "power"
state_class: "measurement"
uom: "W"
scale: 0.1
rule: 4
registers: [0x0014, 0x0015]
validation:
min: 0
max: [24000, 80000]
- name: "Device MPPTs"
attribute:
rule: 1
mask: 0x0F00
divide: 256
registers: [0x0016]
range:
min: 257
validation:
max: 12
default: 2
- name: "Device Phases"
attribute:
rule: 1
mask: 0x000F
registers: [0x0016]
range:
min: 257
validation:
max: 3
default: 3
- name: Device Self-check
attribute:
class: "enum"
rule: 1
registers: [0x0024]
range:
min: 0
max: 1
lookup:
- key: 0x0000
value: "Disabled"
- key: 0x0001
value: "Enabled"
- group: Control
update_interval: 300
items:
- name: "Self-check time"
platform: number
uom: "s"
rule: 1
registers: [0x003D]
range:
min: 0
max: 1000
default: 0
- name: "Date & Time"
platform: datetime
update_interval: 60
rule: 8
registers: [0x003E, 0x003F, 0x0040]
- name: "" # On/Off Switch (Empty name so the sensor has same name as the device, looks good! Can be used once per platform though)
platform: switch
rule: 1
registers: [0x0050]
- group: Settings
update_interval: 300
items:
- name: "Battery Control Mode"
platform: "select"
rule: 1
registers: [0x0062]
icon: "mdi:battery"
lookup:
- key: 0x0000
value: "Lead-Battery, four-stage charging method"
- key: 0x0001
value: "Lithium"
- name: "Battery Equalization"
platform: number
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.01
rule: 1
registers: [0x0063]
configurable:
min: 38
max: 61
step: 0.1
mode: box
icon: "mdi:battery"
range:
min: 3800
max: 6100
- name: "Battery Absorption"
platform: number
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.01
rule: 1
registers: [0x0064]
configurable:
min: 38
max: 61
step: 0.1
mode: box
icon: "mdi:battery"
range:
min: 3800
max: 6100
- name: "Battery Float"
platform: number
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.01
rule: 1
registers: [0x0065]
configurable:
min: 38
max: 61
step: 0.1
mode: box
icon: "mdi:battery"
range:
min: 3800
max: 6100
- name: "Battery Capacity"
platform: number
state_class: "measurement"
uom: "Ah"
rule: 1
registers: [0x0066]
icon: "mdi:battery"
configurable:
mode: box
range:
min: 0
max: 2000
- name: "Battery Empty"
platform: number
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.01
rule: 1
registers: [0x0067]
configurable:
min: 38
max: 61
step: 0.1
mode: box
icon: "mdi:battery"
- name: "Zero Export power"
platform: number
class: "power"
state_class: "measurement"
uom: "W"
rule: 1
registers: [0x0068]
range:
min: 0
max: 65535
configurable:
min: -20
max: 500
icon: "mdi:transmission-tower"
- name: "Battery Equalization Cycle"
platform: number
class: "duration"
state_class: "measurement"
uom: "d"
rule: 1
registers: [0x0069]
icon: "mdi:battery"
configurable:
mode: box
range:
min: 0
max: 90
- name: "Battery Equalization Time"
platform: number
class: "duration"
state_class: "measurement"
uom: "h"
scale: 0.5
rule: 1
registers: [0x006A]
configurable:
min: 0
max: 10
mode: box
icon: "mdi:battery"
range:
min: 0
max: 20
- name: "Battery Temperature Compensation"
platform: number
state_class: "measurement"
uom: "mV/*C"
rule: 2
registers: [0x006B]
configurable:
min: 0
max: 50
step: 0.1
icon: "mdi:battery"
range:
min: 0
max: 50
- name: "Battery Max Charging Current"
platform: number
class: "current"
state_class: "measurement"
uom: "A"
rule: 1
registers: [0x006C]
icon: "mdi:current-dc"
configurable:
mode: box
range:
min: 0
max: 350
- name: "Battery Max Discharging Current"
platform: number
class: "current"
state_class: "measurement"
uom: "A"
rule: 1
registers: [0x006D]
icon: "mdi:current-dc"
configurable:
mode: box
range:
min: 0
max: 350
- name: "Battery Operation Mode"
platform: "select"
rule: 1
registers: [0x006F]
icon: mdi:battery
lookup:
- key: 0x0000
value: Voltage
- key: 0x0001
value: Capacity
- key: 0x0002
value: No Battery
- name: "Battery Wake Up"
platform: "switch"
rule: 1
registers: [0x0081]
value:
on: 0x101
off: 0x00
- name: Battery Resistance
platform: number
state_class: measurement
uom: "mΩ"
rule: 1
registers: [0x0071]
icon: mdi:battery
range:
min: 0
max: 6000
- name: Battery Charging efficiency
platform: number
state_class: measurement
uom: "%"
scale: 0.1
rule: 1
registers: [0x0072]
icon: mdi:battery
configurable:
mode: box
range:
min: 0
max: 1000
validation:
min: 0
max: 100
- name: Battery Shutdown SOC
platform: number
state_class: measurement
uom: "%"
rule: 1
registers: [0x0073]
icon: mdi:battery
configurable:
mode: box
range:
min: 0
max: 100
- name: Battery Restart SOC
platform: number
state_class: measurement
uom: "%"
rule: 1
registers: [0x0074]
icon: mdi:battery
configurable:
mode: box
range:
min: 0
max: 100
- name: Battery Low SOC
platform: number
state_class: measurement
uom: "%"
rule: 1
registers: [0x0075]
icon: mdi:battery
configurable:
mode: box
range:
min: 0
max: 100
- name: Battery Shutdown Voltage
platform: number
class: "voltage"
state_class: measurement
uom: "V"
scale: 0.01
rule: 1
registers: [0x0076]
icon: mdi:battery
configurable:
min: 38
max: 61
step: 0.1
mode: box
range:
min: 3800
max: 6100
- name: Battery Restart Voltage
platform: number
class: "voltage"
state_class: measurement
uom: "V"
scale: 0.01
rule: 1
registers: [0x0077]
icon: mdi:battery
configurable:
min: 38
max: 61
step: 0.1
mode: box
range:
min: 3800
max: 6100
- name: Battery Low Voltage
platform: number
class: "voltage"
state_class: measurement
uom: "V"
scale: 0.01
rule: 1
registers: [0x0078]
icon: mdi:battery
configurable:
min: 38
max: 61
step: 0.1
mode: box
range:
min: 3800
max: 6100
- name: "Generator Operating Time"
platform: number
class: "duration"
state_class: "measurement"
uom: "h"
scale: 0.1
rule: 1
registers: [0x0079]
icon: "mdi:generator-stationary"
configurable:
min: 0
max: 24
mode: box
range:
min: 0
max: 240
- name: "Generator Cooling Time"
platform: number
class: "duration"
state_class: "measurement"
uom: "h"
scale: 0.1
rule: 1
registers: [0x007A]
icon: "mdi:generator-stationary"
configurable:
min: 0
max: 24
mode: box
range:
min: 0
max: 240
- name: Battery Generator Charging Start Voltage
platform: number
class: "voltage"
state_class: measurement
uom: "V"
scale: 0.01
rule: 1
registers: [0x007B]
icon: mdi:battery
configurable:
min: 00
max: 63
step: 0.1
mode: box
range:
min: 0000
max: 6300
- name: Battery Generator Charging Start
platform: number
state_class: measurement
uom: "%"
rule: 1
registers: [0x007C]
icon: mdi:battery
configurable:
mode: box
range:
min: 0
max: 100
- name: "Battery Generator Charging Current"
platform: number
class: "current"
state_class: "measurement"
uom: "A"
rule: 1
registers: [0x007D]
icon: "mdi:current-dc"
configurable:
mode: box
range:
min: 0
max: 240
- name: "Battery Grid Charging Start Voltage"
platform: number
class: "voltage"
state_class: measurement
uom: "V"
scale: 0.01
rule: 1
registers: [0x007E]
icon: "mdi:battery"
configurable:
min: 00
max: 63
step: 0.1
mode: box
range:
min: 0000
max: 6300
- name: "Battery Grid Charging Start"
platform: number
state_class: measurement
uom: "%"
rule: 1
registers: [0x007F]
icon: "mdi:battery"
configurable:
mode: box
range:
min: 0
max: 100
- name: "Battery Grid Charging Current"
platform: number
class: "current"
state_class: "measurement"
uom: "A"
rule: 1
registers: [0x0080]
icon: "mdi:current-dc"
configurable:
mode: box
range:
min: 0
max: 350
- name: "Battery Generator Charging"
platform: "switch"
rule: 1
registers: [0x0081]
icon: "mdi:battery"
- name: "Battery Grid Charging"
platform: "switch"
rule: 1
registers: [0x0082]
icon: "mdi:battery"
- name: "Generator"
name_lookup: "io_mode_select"
platform: "switch"
rule: 1
registers: [0x0084]
- name: "Generator Force On"
platform: "switch"
rule: 1
registers: [0x005d]
value:
on: 0x11
off: 0x00
- name: "IO Mode"
alt: Generator input mode
description: The Generator/SmartLoad/Microinverter input-output mode
platform: "select"
rule: 1
registers: [0x0085]
icon: "mdi:lightning-bolt-circle"
lookup:
- key: 0x0000
value: "Generator"
- key: 0x0001
value: "SmartLoad"
- key: 0x0002
value: "Microinverter"
- name: "SmartLoad Off Voltage"
platform: number
class: "voltage"
state_class: measurement
uom: "V"
scale: 0.01
rule: 1
registers: [0x0086]
icon: "mdi:battery"
configurable:
min: 38
max: 63
step: 0.1
mode: box
range:
min: 3800
max: 6300
- name: "SmartLoad Off"
platform: number
state_class: "measurement"
uom: "%"
rule: 1
registers: [0x0087]
icon: "mdi:lightning-bolt-circle"
configurable:
mode: box
range:
min: 0
max: 100
- name: "SmartLoad On Voltage"
platform: number
class: "voltage"
state_class: measurement
uom: "V"
scale: 0.01
rule: 1
registers: [0x0088]
icon: "mdi:battery"
configurable:
min: 38
max: 63
step: 0.1
mode: box
range:
min: 3800
max: 6300
- name: "SmartLoad On"
platform: number
state_class: "measurement"
uom: "%"
rule: 1
registers: [0x0089]
icon: "mdi:lightning-bolt-circle"
configurable:
mode: box
range:
min: 0
max: 100
- group: Grid Parameters
update_interval: 300
items:
- name: Grid Voltage
platform: "select"
registers: [0x008A]
rule: 1
lookup:
- key: 0x0
value: LN:220VAC LL:380VAC
- key: 0x1
value: LN:230VAC LL:398VAC
- key: 0x2
value: LN:240VAC LL:415VAC
- key: 0x3
value: LN:120VAC LL:208VAC
- key: 0x4
value: LN:133VAC LL:220VAC
- key: 0x5
value: LN:100VAC LL:173VAC
- name: "Generator Min PV Power"
name_lookup: "io_mode_select"
enabled_lookup:
io_mode_select: [Generator, SmartLoad]
platform: number
class: "power"
state_class: "measurement"
uom: "W"
rule: 1
registers: [0x008B]
icon: "mdi:solar-power-variant"
range:
min: 0000
max: 8000
- name: Charging Signal
platform: "select"
rule: 1
registers: [0x008C]
lookup:
- key: 0x0000
value: "Normal"
- key: 0x0001
value: "Grid"
- key: 0x0002
value: "Generator"
- key: 0x0003
value: "Both"
- group: Work Mode
update_interval: 300
items:
- name: Energy Pattern
platform: "select"
rule: 1
registers: [0x008D]
lookup:
- key: 0x0000
value: "Battery First"
- key: 0x0001
value: "Load First"
- name: Work Mode
platform: "select"
rule: 1
registers: [0x008E]
lookup:
- key: 0x0000
value: "Export First"
- key: 0x0001
value: "Zero Export To Load"
- key: 0x0002
value: "Zero Export To CT"
- name: Export Surplus Power
alt: Max Sell Power
platform: number
class: "power"
state_class: "measurement"
uom: "W"
scale: [1, 10]
rule: 1
registers: [0x008F]
configurable:
min: 0
max: [24000, 80000]
range:
min: 0
max: [24000, 8000]
- name: Export Surplus
alt: Solar Sell
platform: "switch"
rule: 1
registers: [0x0091]
- name: Export Asymmetry
alt: Asymmetric phase feeding
platform: switch
rule: 1
registers: [0x00ED]
- name: PV Power
description: Max PV power limiter
alt: Max Solar Power
platform: number
class: "power"
state_class: "measurement"
uom: "W"
scale: [1, 10]
rule: 1
registers: [0x0154]
icon: "mdi:solar-power-variant"
configurable:
min: 0
max: [32000, 128000]
range:
min: 0
max: [32000, 12800]
- name: MPPT multi-point scanning
description: Find the MPP even when there are partial shading conditions on the solar panels
platform: "switch"
rule: 1
registers: [0x0155]
value:
bit: 2
- name: Time of Use
platform: select
rule: 1
registers: [0x0092]
lookup:
- key: 0x0000
value: "Disabled"
- key: 0x0003
value: "Monday"
- key: 0x0005
value: "Tuesday"
- key: 0x0009
value: "Wednesday"
- key: 0x0011
value: "Thursday"
- key: 0x0021
value: "Friday"
- key: 0x0041
value: "Saturday"
- key: 0x0081
value: "Sunday"
- key: 0x003F
value: "Weekdays"
- key: 0x00C1
value: "Weekend"
- key: 0x00FD
value: "Week -Monday"
- key: 0x00FB
value: "Week -Tuesday"
- key: 0x00F7
value: "Week -Wednesday"
- key: 0x00EF
value: "Week -Thursday"
- key: 0x00DF
value: "Week -Friday"
- key: 0x00BF
value: "Week -Saturday"
- key: 0x007F
value: "Week -Sunday"
- key: 0x00FF
value: "Week"
- bit: 0
mode: "|"
value: "Enabled"
- name: Program 1 Time
platform: "time"
state_class: measurement
rule: 9
registers: [0x0094]
range:
min: 0000
max: 2359
icon: mdi:sun-clock
- name: Program 2 Time
platform: "time"
state_class: measurement
rule: 9
registers: [0x0095]
range:
min: 0000
max: 2359
icon: mdi:sun-clock
- name: Program 3 Time
platform: "time"
state_class: measurement
rule: 9
registers: [0x0096]
range:
min: 0000
max: 2359
icon: mdi:sun-clock
- name: Program 4 Time
platform: "time"
state_class: measurement
rule: 9
registers: [0x0097]
range:
min: 0000
max: 2359
icon: mdi:sun-clock
- name: Program 5 Time
platform: "time"
state_class: measurement
rule: 9
registers: [0x0098]
range:
min: 0000
max: 2359
icon: mdi:sun-clock
- name: Program 6 Time
platform: "time"
state_class: measurement
rule: 9
registers: [0x0099]
range:
min: 0000
max: 2359
icon: mdi:sun-clock
- name: Program 1 Power
platform: number
class: "power"
state_class: measurement
uom: "W"
scale: [1, 10]
rule: 1
registers: [0x009A]
icon: mdi:sun-clock
configurable:
min: 0
max: [32000, 128000]
range:
min: 0
max: [32000, 12800]
- name: Program 2 Power
platform: number
class: "power"
state_class: measurement
uom: "W"
scale: [1, 10]
rule: 1
registers: [0x009B]
icon: mdi:sun-clock
configurable:
min: 0
max: [32000, 128000]
range:
min: 0
max: [32000, 12800]
- name: Program 3 Power
platform: number
class: "power"
state_class: measurement
uom: "W"
scale: [1, 10]
rule: 1
registers: [0x009C]
icon: mdi:sun-clock
configurable:
min: 0
max: [32000, 128000]
range:
min: 0
max: [32000, 12800]
- name: Program 4 Power
platform: number
class: "power"
state_class: measurement
uom: "W"
scale: [1, 10]
rule: 1
registers: [0x009D]
icon: mdi:sun-clock
configurable:
min: 0
max: [32000, 128000]
range:
min: 0
max: [32000, 12800]
- name: Program 5 Power
platform: number
class: "power"
state_class: measurement
uom: "W"
scale: [1, 10]
rule: 1
registers: [0x009E]
icon: mdi:sun-clock
configurable:
min: 0
max: [32000, 128000]
range:
min: 0
max: [32000, 12800]
- name: Program 6 Power
platform: number
class: "power"
state_class: measurement
uom: "W"
scale: [1, 10]
rule: 1
registers: [0x009F]
icon: mdi:sun-clock
configurable:
min: 0
max: [32000, 128000]
range:
min: 0
max: [32000, 12800]
- name: Program 1 Voltage
platform: number
class: "voltage"
state_class: measurement
uom: "V"
scale: 0.01
rule: 1
registers: [0x00A0]
configurable:
min: 00
max: 61
step: 0.1
mode: box
range:
min: 0000
max: 6100
icon: mdi:sun-clock
- name: Program 2 Voltage
platform: number
class: "voltage"
state_class: measurement
uom: "V"
scale: 0.01
rule: 1
registers: [0x00A1]
configurable:
min: 00
max: 61
step: 0.1
mode: box
range:
min: 0000
max: 6100
icon: mdi:sun-clock
- name: Program 3 Voltage
platform: number
class: "voltage"
state_class: measurement
uom: "V"
scale: 0.01
rule: 1
registers: [0x00A2]
configurable:
min: 00
max: 61
step: 0.1
mode: box
range:
min: 0000
max: 6100
icon: mdi:sun-clock
- name: Program 4 Voltage
platform: number
class: "voltage"
state_class: measurement
uom: "V"
scale: 0.01
rule: 1
registers: [0x00A3]
configurable:
min: 00
max: 61
step: 0.1
mode: box
range:
min: 0000
max: 6100
icon: mdi:sun-clock
- name: Program 5 Voltage
platform: number
class: "voltage"
state_class: measurement
uom: "V"
scale: 0.01
rule: 1
registers: [0x00A4]
configurable:
min: 00
max: 61
step: 0.1
mode: box
range:
min: 0000
max: 6100
icon: mdi:sun-clock
- name: Program 6 Voltage
platform: number
class: "voltage"
state_class: measurement
uom: "V"
scale: 0.01
rule: 1
registers: [0x00A5]
configurable:
min: 00
max: 61
step: 0.1
mode: box
range:
min: 0000
max: 6100
icon: mdi:sun-clock
- name: Program 1 SOC
platform: number
state_class: measurement
uom: "%"
rule: 1
registers: [0x00A6]
configurable:
mode: box
range:
min: 0
max: 100
icon: mdi:sun-clock
- name: Program 2 SOC
platform: number
state_class: measurement
uom: "%"
rule: 1
registers: [0x00A7]
configurable:
mode: box
range:
min: 0
max: 100
icon: mdi:sun-clock
- name: Program 3 SOC
platform: number
state_class: measurement
uom: "%"
rule: 1
registers: [0x00A8]
configurable:
mode: box
range:
min: 0
max: 100
icon: mdi:sun-clock
- name: Program 4 SOC
platform: number
state_class: measurement
uom: "%"
rule: 1
registers: [0x00A9]
configurable:
mode: box
range:
min: 0
max: 100
icon: mdi:sun-clock
- name: Program 5 SOC
platform: number
state_class: measurement
uom: "%"
rule: 1
registers: [0x00AA]
configurable:
mode: box
range:
min: 0
max: 100
icon: mdi:sun-clock
- name: Program 6 SOC
platform: number
state_class: measurement
uom: "%"
rule: 1
registers: [0x00AB]
configurable:
mode: box
range:
min: 0
max: 100
icon: mdi:sun-clock
- name: Program 1 Charging
platform: select
rule: 1
registers: [0x00AC]
icon: mdi:sun-clock
lookup:
- key: 0x0000
value: "Disabled"
- key: 0x0001
value: "Grid"
- key: 0x0002
value: "Generator"
- key: 0x0003
value: "Both"
- name: Program 2 Charging
platform: select
rule: 1
registers: [0x00AD]
icon: mdi:sun-clock
lookup:
- key: 0x0000
value: "Disabled"
- key: 0x0001
value: "Grid"
- key: 0x0002
value: "Generator"
- key: 0x0003
value: "Both"
- name: Program 3 Charging
platform: select
rule: 1
registers: [0x00AE]
icon: mdi:sun-clock
lookup:
- key: 0x0000
value: "Disabled"
- key: 0x0001
value: "Grid"
- key: 0x0002
value: "Generator"
- key: 0x0003
value: "Both"
- name: Program 4 Charging
platform: select
rule: 1
registers: [0x00AF]
icon: mdi:sun-clock
lookup:
- key: 0x0000
value: "Disabled"
- key: 0x0001
value: "Grid"
- key: 0x0002
value: "Generator"
- key: 0x0003
value: "Both"
- name: Program 5 Charging
platform: select
rule: 1
registers: [0x00B0]
icon: mdi:sun-clock
lookup:
- key: 0x0000
value: "Disabled"
- key: 0x0001
value: "Grid"
- key: 0x0002
value: "Generator"
- key: 0x0003
value: "Both"
- name: Program 6 Charging
platform: select
rule: 1
registers: [0x00B1]
icon: mdi:sun-clock
lookup:
- key: 0x0000
value: "Disabled"
- key: 0x0001
value: "Grid"
- key: 0x0002
value: "Generator"
- key: 0x0003
value: "Both"
- name: Microinverter Export cut-off
platform: "switch"
rule: 1
registers: [0x00B2]
value:
bit: 0
- name: Generator Peak shaving
platform: "switch"
rule: 1
registers: [0x00B2]
value:
bit: 2
- name: Grid Peak shaving
platform: "switch"
rule: 1
registers: [0x00B2]
value:
bit: 4
- name: Generator On-Grid
description: On Grid always on
name_lookup: io_mode_select
enabled_lookup:
io_mode_select: [Generator, SmartLoad]
platform: "switch"
rule: 1
registers: [0x00B2]
value:
bit: 6
- name: Off Grid
platform: switch
rule: 1
range:
min: 0
max: 1
registers: [0x00B3]
- name: Grid Frequency
platform: "select"
rule: 1
registers: [0x00B7]
lookup:
- key: 0x0
value: 50 Hz
- key: 0x1
value: 60 Hz
- name: "Grid voltage protection - high"
platform: number
class: "voltage"
uom: "V"
scale: 0.1
rule: 1
registers: [0x00B9]
configurable:
mode: box
range:
min: 1000
max: 2900
- name: "Grid voltage protection - low"
platform: number
class: "voltage"
uom: "V"
scale: 0.1
rule: 1
registers: [0x00BA]
configurable:
mode: box
range:
min: 1000
max: 2900
- name: "Grid frequency protection - high"
platform: number
class: "frequency"
uom: "Hz"
scale: 0.01
rule: 1
registers: [0x00BB]
configurable:
mode: box
range:
min: 4500
max: 6500
- name: "Grid frequency protection - low"
platform: number
class: "frequency"
uom: "Hz"
scale: 0.01
rule: 1
registers: [0x00BC]
configurable:
mode: box
range:
min: 4500
max: 6500
- name: Generator Grid side
description: The generator is connected to the grid input
platform: "switch"
rule: 1
registers: [0x00BD]
- name: "Generator Peak shaving"
platform: number
class: "power"
uom: "W"
scale: [1, 10]
rule: 1
registers: [0x00BE]
icon: "mdi:generator-stationary"
configurable:
min: 0
max: 22000
range:
min: 0
max: [22000, 2200]
- name: "Grid Peak shaving"
platform: number
class: "power"
uom: "W"
scale: [1, 10]
rule: 1
registers: [0x00BF]
icon: "mdi:transmission-tower"
configurable:
min: 0
max: 80000
range:
min: 0
max: [80000, 8000]
- name: "Grid Max Export power"
platform: number
class: "power"
uom: "W"
scale: 10
rule: 1
registers: [0x00E7]
range:
min: 0
max: 8000
- name: "Grid Max Import power"
platform: number
class: "power"
uom: "W"
scale: 10
rule: 1
registers: [0x00E9]
range:
min: 0
max: 8000
- name: AC Coupling
description: Couple inverters and batteries using AC lines
platform: "select"
rule: 1
registers: [0x00EA]
lookup:
- key: 0
value: Disabled
- bit: 0
value: Grid
- bit: 1
value: Load
- group: BMS
items:
- name: "Battery BMS Charging Voltage"
attribute:
class: "voltage"
state_class: "measurement"
uom: "V"
scale: [0.01, 0.1]
rule: 1
registers: [0x00D2]
- name: "Battery BMS Discharging Voltage"
attribute:
class: "voltage"
state_class: "measurement"
uom: "V"
scale: [0.01, 0.1]
rule: 1
registers: [0x00D3]
- name: "Battery BMS Charging Current"
attribute:
class: "current"
state_class: "measurement"
uom: "A"
rule: 1
registers: [0x00D4]
icon: "mdi:current-dc"
- name: "Battery BMS Discharging Current"
attribute:
class: "current"
state_class: "measurement"
uom: "A"
rule: 1
registers: [0x00D5]
icon: "mdi:current-dc"
- name: "Battery BMS SOC"
attribute:
state_class: "measurement"
uom: "%"
rule: 1
registers: [0x00D6]
icon: "mdi:battery"
validation:
min: 0
max: 101
- name: "Battery BMS Voltage"
attribute:
class: "voltage"
state_class: "measurement"
uom: "V"
scale: [0.01, 0.1]
rule: 1
registers: [0x00D7]
- name: "Battery BMS Current"
attribute:
class: "current"
state_class: "measurement"
uom: "A"
scale: [1, 0.1]
rule: 2
registers: [0x00D8]
icon: "mdi:current-dc"
- name: "Battery BMS Max Charging Current"
attribute:
class: "current"
state_class: "measurement"
uom: "A"
rule: 1
registers: [0x00DA]
icon: "mdi:current-dc"
- name: "Battery BMS Max Discharging Current"
attribute:
class: "current"
state_class: "measurement"
uom: "A"
rule: 1
registers: [0x00DB]
icon: "mdi:current-dc"
- name: "Battery Alarm"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x00DC]
icon: "mdi:battery-alert"
attributes: ["value"]
- name: "Battery Fault"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x00DD]
icon: "mdi:battery-alert-variant"
range:
min: 0
max: 65535
attributes: ["value"]
- name: "Battery BMS Other Symbol"
attribute:
rule: 1
registers: [0x00DE]
icon: "mdi:battery-unknown"
range:
min: 0
max: 65535
- name: Battery BMS Type
platform: select
rule: 1
registers: [0x00DF]
icon: "mdi:battery"
lookup:
- key: 0x0000
value: "PYLON"
- key: 0x0001
value: "Tianbangda"
- key: 0x0002
value: "KOK"
- key: 0x0003
value: "Keith"
- key: 0x0004
value: "Toppai"
- key: 0x0005
value: "Peneng 485"
- key: 0x0006
value: "Jeris 485"
- key: 0x0007
value: "Sunwoda 485"
- key: 0x0008
value: "Xinrui 485"
- key: 0x0009
value: "Tianbangda 485"
- key: 0x000A
value: "Shenggao Electric CAN"
- group: Meter
update_interval: 30
items:
- name: Today Battery Charge
alt: Daily Battery Charge
friendly_name: Today's Battery Charge
class: "energy"
state_class: "total_increasing"
uom: "kWh"
scale: 0.1
rule: 1
registers: [0x0202]
icon: "mdi:battery-plus"
- name: Today Battery Discharge
alt: Daily Battery Discharge
friendly_name: Today's Battery Discharge
class: "energy"
state_class: "total_increasing"
uom: "kWh"
scale: 0.1
rule: 1
registers: [0x0203]
icon: "mdi:battery-minus"
- name: "Total Battery Charge"
class: "energy"
state_class: "total_increasing"
uom: "kWh"
scale: 0.1
rule: 3
registers: [0x0204, 0x0205]
icon: "mdi:battery-plus"
validation:
min: 0.1
- name: "Total Battery Discharge"
class: "energy"
state_class: "total_increasing"
uom: "kWh"
scale: 0.1
rule: 3
registers: [0x0206, 0x0207]
icon: "mdi:battery-minus"
validation:
min: 0.1
- name: Today Battery Life Cycles
alt: Daily Battery Life Cycles
friendly_name: Today's Battery Life Cycles
description: Calculates today's battery life cycles based on today's charged amount
state_class: "total_increasing"
rule: 0
digits: 2
icon: "mdi:battery-sync"
- name: "Total Battery Life Cycles"
description: Calculates total battery life cycles based on total charged amount
state_class: "total_increasing"
rule: 0
digits: 2
icon: "mdi:battery-sync"
validation:
min: 0.1
- name: Today Energy Import
alt: Daily Energy Bought
friendly_name: Today's Energy Import
description: Today's energy imported from the grid
class: "energy"
state_class: "total_increasing"
uom: "kWh"
scale: 0.1
rule: 1
registers: [0x0208]
icon: "mdi:transmission-tower-export"
- name: Today Energy Export
alt: Daily Energy Sold
friendly_name: Today's Energy Export
description: Today's energy exported/returned to the grid
class: "energy"
state_class: "total_increasing"
uom: "kWh"
scale: 0.1
rule: 1
registers: [0x0209]
icon: "mdi:transmission-tower-import"
- name: Total Energy Import
alt: Total Energy Bought
description: Total energy imported from the grid
class: "energy"
state_class: "total_increasing"
uom: "kWh"
scale: 0.1
rule: 3
registers: [0x020A, 0x020B]
icon: "mdi:transmission-tower-export"
validation:
min: 0.1
- name: Total Energy Export
alt: Total Energy Sold
description: Total energy exported/returned to the grid
class: "energy"
state_class: "total_increasing"
uom: "kWh"
scale: 0.1
rule: 3
registers: [0x020C, 0x020D]
icon: "mdi:transmission-tower-import"
validation:
min: 0.1
- name: Today Load Consumption
alt: Daily Load Consumption
friendly_name: Today's Load Consumption
class: "energy"
state_class: "total_increasing"
uom: "kWh"
scale: 0.1
rule: 1
registers: [0x020E]
- name: "Total Load Consumption"
class: "energy"
state_class: "total_increasing"
uom: "kWh"
scale: 0.1
rule: 3
registers: [0x020F, 0x0210]
validation:
min: 0.1
- name: Generator Energy - today
name_lookup: "io_mode_select"
class: "energy"
state_class: "total_increasing"
uom: "kWh"
scale: 0.1
rule: 1
registers: [0x0218]
- name: Generator Energy
name_lookup: "io_mode_select"
class: "energy"
state_class: "total_increasing"
uom: "kWh"
scale: 0.1
rule: 3
registers: [0x0219, 0x021A]
validation:
min: 0.1
- name: Today Production
alt: Daily Production
friendly_name: Today's Production
class: "energy"
state_class: "total_increasing"
uom: "kWh"
scale: 0.1
rule: 1
registers: [0x0211]
icon: "mdi:solar-power"
validation:
dev: 100
invalidate_all: 2
- name: "Total Production"
class: "energy"
state_class: "total_increasing"
uom: "kWh"
scale: 0.1
rule: 3
registers: [0x0216, 0x0217]
icon: "mdi:solar-power"
validation:
min: 0.1
dev: 100
invalidate_all: 2
- name: Today Losses
alt: Daily Losses
friendly_name: Today's Losses
description: Includes today's consumption of the inverter device itself as well AC/DC conversion losses
class: "energy"
state_class: "total_increasing"
ensure_increasing:
uom: "kWh"
rule: 1
digits: 1
scale: 0.1
uint: enforce
sensors:
- registers: [0x0208]
- registers: [0x0211]
- registers: [[], [0x0218]]
enabled_lookup:
io_mode_select: [Generator, Microinverter]
- registers: [0x0203]
- operator: subtract
registers: [0x0209]
- operator: subtract
registers: [0x020E]
- operator: subtract
registers: [0x0202]
- name: Total Losses
description: Includes total consumption of the inverter device itself as well AC/DC conversion losses
class: "energy"
state_class: "total_increasing"
ensure_increasing:
uom: "kWh"
rule: 3
digits: 1
scale: 0.1
uint: enforce
sensors:
- registers: [0x020A, 0x020B]
- registers: [0x0216, 0x0217]
- registers: [[], [0x0219, 0x021A]]
enabled_lookup:
io_mode_select: [Generator, Microinverter]
- registers: [0x0206, 0x0207]
- operator: subtract
registers: [0x020C, 0x020D]
- operator: subtract
registers: [0x020F, 0x0210]
- operator: subtract
registers: [0x0204, 0x0205]
validation:
min: 1
- name: "DC Temperature"
hidden:
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 2
offset: 1000
registers: [0x021C]
icon: "mdi:thermometer"
range:
min: 0
max: 3000
- name: "Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 2
offset: 1000
registers: [0x021D]
icon: "mdi:thermometer"
range:
min: 0
max: 3000
- group: State
update_interval: 30
items:
- name: "Device State"
class: "enum"
rule: 1
registers: [0x01F4]
icon: "mdi:state-machine"
range:
min: 0
max: 5
lookup:
- key: 0x0000
value: "Standby"
- key: 0x0001
value: "Self-test"
- key: 0x0002
value: "Normal"
- key: 0x0003
value: "Alarm"
- key: 0x0004
value: "Fault"
- name: "" # Power On/Off (Empty name so the sensor has same name as the device, looks good! Can be used once per platform though)
platform: "binary_sensor"
device_class: running
rule: 1
registers: [0x0227]
- name: "Device Relay"
class: "enum"
rule: 1
registers: [0x0228]
icon: "mdi:directions-fork"
lookup:
- key: 0x0000
value: "Off"
- key: [0x0001, 0x0003]
value: "Inverter"
- key: [0x0004, 0x0006]
value: "Grid"
- key: [0x0005, 0x0007]
value: "Inverter-Grid"
- key: 0x0008
value: "Generator"
- key: [0x0009, 0x000B]
value: "Inverter-Gen"
- key: [0x000C, 0x000E]
value: "Grid-Generator"
- key: [0x000D, 0x000F]
value: "Inv-Grid-Gen"
- key: default
value: "Power Supply"
- name: "Grid"
platform: "binary_sensor"
device_class: power
rule: 1
registers: [0x0228]
bit: 2
icon: "mdi:transmission-tower"
- name: "Generator"
name_lookup: "io_mode_select"
platform: "binary_sensor"
device_class: power
rule: 1
registers: [0x0228]
bit: 3
icon: "mdi:lightning-bolt-circle"
# Alarm message (word 1 & 2) [0, 65535]
- name: "Device Alarm"
class: "enum"
rule: 3
registers: [0x0229, 0x022A]
icon: "mdi:alert-outline"
lookup:
- key: 0
value: "OK"
- bit: 1
value: "Fan failure"
- bit: 2
value: "Grid phase failure"
- bit: 3
value: "Meter communication failure"
- bit: 30
value: "Battery loss"
- bit: 31
value: "Parallel communication quality"
- key: default
value: Problem
# Fault message (word 1, 2, 3 & 4) [0, 65535]
- name: "Device Fault"
class: "enum"
rule: 3
registers: [0x22B, 0x022C, 0x022D, 0x022E]
icon: "mdi:message-alert-outline"
lookup:
- key: 0
value: "OK"
- bit: 6
value: "DC/DC Soft Start failure"
- bit: 9
value: "Auxiliary power supply failure"
- bit: 12
value: "Working mode changed"
- bit: 17
value: "AC Over-current failure"
- bit: 18
value: "Tz_Integ_Fault failure"
- bit: 19
value: "DC Over-current failure"
- bit: 22
value: "AC current leakage failure"
- bit: 63
value: "Temperature is too high"
- key: default
value: Problem
- group: Battery
update_interval: 5
items:
# Battery - The temperature of battery 1
- name: "Battery Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x024A]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
# Battery - The voltage of battery 1 (L:0.01V, H:0.1V)
- name: "Battery Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: [0.01, 0.1]
rule: 1
registers: [0x024B]
# Battery - The State of Charge (SOC) of battery 1
- name: "Battery"
class: "battery"
state_class: "measurement"
uom: "%"
rule: 1
registers: [0x024C]
range:
min: 0
max: 100
validation:
min: 0
max: 101
attributes:
[
"Battery Corrected Capacity",
"Battery BMS SOC",
"Battery BMS Current",
"Battery BMS Voltage",
"Battery BMS Other Symbol",
"Battery BMS Charging Voltage",
"Battery BMS Discharging Voltage",
"Battery BMS Charging Current",
"Battery BMS Discharging Current",
"Battery BMS Max Charging Current",
"Battery BMS Max Discharging Current",
]
# Battery - The power of battery is S16bit
- name: "Battery Power"
class: "power"
state_class: "measurement"
uom: "W"
scale: [1, 10]
rule: 2
registers: [0x024E]
attributes: [inverse]
# Battery - The state of health
- name: "Battery SOH"
description: Calculates state of health based on total charged amount
state_class: "measurement"
uom: "%"
rule: 0
digits: 2
icon: "mdi:battery-heart"
# Battery - Capacity
- name: "Battery Capacity"
description: Estimates capacity of the battery during (dis)charging
class: energy_storage
state_class: measurement
uom: "kWh"
rule: 0
digits: 1
icon: "mdi:battery-check"
# Battery - The state of battery
- name: "Battery State"
description: Determines battery state from battery power by +-50 W
class: "enum"
rule: 0
options: ["charging", "idle", "discharging"]
icon: "mdi:battery"
# Battery - The current of battery 1 is S16bit (low 16 bits)
- name: "Battery Current"
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.01
rule: 2
sensors:
- signed:
registers: [0x024F]
- signed:
registers: [0x0252]
icon: "mdi:current-dc"
# Battery - Actual capacity of the battery
- name: "Battery Corrected Capacity"
attribute:
state_class: "measurement"
uom: "Ah"
rule: 1
registers: [0x0250]
icon: "mdi:battery"
range:
min: 0
max: 3000
- group: Grid
update_interval: 5
items:
# Grid side - The voltage of phase A
- name: "Grid L1 Voltage"
l: 1
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x0256]
icon: "mdi:transmission-tower"
# Grid side - The voltage of phase B
- name: "Grid L2 Voltage"
l: 2
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x0257]
icon: "mdi:transmission-tower"
# Grid side - The voltage of phase C
- name: "Grid L3 Voltage"
l: 3
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x0258]
icon: "mdi:transmission-tower"
# Grid internal - The power of phase A is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "Internal CT1 Power"
l: 1
class: "power"
state_class: "measurement"
uom: "W"
rule: 4
registers: [0x025C, 0x02BC]
icon: "mdi:transmission-tower"
# Grid internal - The power of phase B is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "Internal CT2 Power"
l: 2
class: "power"
state_class: "measurement"
uom: "W"
rule: 4
registers: [0x025D, 0x02BD]
icon: "mdi:transmission-tower"
# Grid internal - The power of phase C is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "Internal CT3 Power"
l: 3
class: "power"
state_class: "measurement"
uom: "W"
rule: 4
registers: [0x025E, 0x02BE]
icon: "mdi:transmission-tower"
# Grid internal - The power is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "Internal Power"
l: 1
class: "power"
state_class: "measurement"
uom: "W"
rule: 4
registers: [0x025F, 0x02BF]
icon: "mdi:transmission-tower"
- name: "Grid Frequency"
l: 1
class: "frequency"
state_class: "measurement"
uom: "Hz"
scale: 0.01
rule: 1
registers: [0x0261]
# Grid internal - The current of phase A is S16bit (low 16 bits)
- name: "Internal CT1 Current"
l: 1
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.01
rule: 2
registers: [0x0262]
icon: "mdi:transmission-tower"
# Grid internal - The current of phase B is S16bit (low 16 bits)
- name: "Internal CT2 Current"
l: 2
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.01
rule: 2
registers: [0x0263]
icon: "mdi:transmission-tower"
# Grid internal - The current of phase C is S16bit (low 16 bits)
- name: "Internal CT3 Current"
l: 3
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.01
rule: 2
registers: [0x0264]
icon: "mdi:transmission-tower"
# Grid external - The current of phase A is S16bit (low 16 bits)
- name: "External CT1 Current"
l: 1
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.01
rule: 2
registers: [0x0265]
icon: "mdi:transmission-tower"
# Grid external - The current of phase B is S16bit (low 16 bits)
- name: "External CT2 Current"
l: 2
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.01
rule: 2
registers: [0x0266]
icon: "mdi:transmission-tower"
# Grid external - The current of phase C is S16bit (low 16 bits)
- name: "External CT3 Current"
l: 3
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.01
rule: 2
registers: [0x0267]
icon: "mdi:transmission-tower"
# Grid external - The power of phase A is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "External CT1 Power"
l: 1
class: "power"
state_class: "measurement"
uom: "W"
rule: 4
registers: [0x0268, 0x02C1]
icon: "mdi:transmission-tower"
# Grid external - The power of phase B is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "External CT2 Power"
l: 2
class: "power"
state_class: "measurement"
uom: "W"
rule: 4
registers: [0x0269, 0x02C2]
icon: "mdi:transmission-tower"
# Grid external - The power of phase C is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "External CT3 Power"
l: 3
class: "power"
state_class: "measurement"
uom: "W"
rule: 4
registers: [0x026A, 0x02C3]
icon: "mdi:transmission-tower"
# Grid external - The power is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "External Power"
l: 1
class: "power"
state_class: "measurement"
uom: "W"
rule: 4
registers: [0x026B, 0x02C4]
icon: "mdi:transmission-tower"
- name: "Grid Power Factor"
platform: number
class: "power_factor"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x026D]
configurable:
mode: box
range:
min: 0
max: 1000
icon: "mdi:transmission-tower"
# The following three (four) registers change according to the built-in and external settings
# Grid - The power of phase A is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "Grid L1 Power"
l: 1
class: "power"
state_class: "measurement"
uom: "W"
rule: 4
registers: [0x026E, 0x02AF]
icon: "mdi:transmission-tower"
# Grid - The power of phase A is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "Grid L2 Power"
l: 2
class: "power"
state_class: "measurement"
uom: "W"
rule: 4
registers: [0x026F, 0x02B0]
icon: "mdi:transmission-tower"
# Grid - The power of phase A is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "Grid L3 Power"
l: 3
class: "power"
state_class: "measurement"
uom: "W"
rule: 4
registers: [0x0270, 0x02B1]
icon: "mdi:transmission-tower"
# Grid - The power is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "Grid Power"
l: 1
description: Combined power of all three phases
class: "power"
state_class: "measurement"
uom: "W"
rule: 4
registers: [0x0271, 0x02B2]
icon: "mdi:transmission-tower"
attributes: [inverse]
- group: Output
update_interval: 5
items:
# Output - The voltage of phase A
- name: "Output L1 Voltage"
l: 1
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x0273]
# Output - The voltage of phase B
- name: "Output L2 Voltage"
l: 2
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x0274]
# Output - The voltage of phase C
- name: "Output L3 Voltage"
l: 3
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x0275]
# Output - The current of phase A is S16bit (low 16 bits)
- name: "Output L1 Current"
l: 1
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.01
rule: 2
registers: [0x0276]
# Output - The current of phase B is S16bit (low 16 bits)
- name: "Output L2 Current"
l: 2
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.01
rule: 2
registers: [0x0277]
# Output - The current of phase C is S16bit (low 16 bits)
- name: "Output L3 Current"
l: 3
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.01
rule: 2
registers: [0x0278]
# Output - The power of phase A is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "Output L1 Power"
l: 1
class: "power"
state_class: "measurement"
uom: "W"
rule: 4
registers: [0x0279, 0x02B3]
# Output - The power of phase B is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "Output L2 Power"
l: 2
class: "power"
state_class: "measurement"
uom: "W"
rule: 4
registers: [0x027A, 0x02B4]
# Output - The power of phase C is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "Output L3 Power"
l: 3
class: "power"
state_class: "measurement"
uom: "W"
rule: 4
registers: [0x027B, 0x02B5]
# Output - The power is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "Power"
alt: Output Power
class: "power"
state_class: "measurement"
uom: "W"
rule: 4
registers: [0x027C, 0x02B6]
- name: "Power losses"
description: Includes consumption of the inverter device itself as well AC/DC conversion losses
class: "power"
state_class: "measurement"
uom: "W"
rule: 1
digits: 0
scale: [1, 10]
uint: enforce
sensors:
- signed:
registers: [0x024E]
- registers: [0x02A0]
- registers: [0x02A1]
- registers: [0x02A2]
- registers: [0x02A3]
- operator: subtract
signed:
scale: 1
registers: [0x027C, 0x02B6]
- name: "Output Frequency"
l: 1
class: "frequency"
state_class: "measurement"
uom: "Hz"
scale: 0.01
rule: 1
registers: [0x027E]
- group: UPS
update_interval: 5
items:
# Load UPS output - The power of phase A is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "Load UPS L1 Power"
l: 1
hidden:
class: "power"
state_class: "measurement"
uom: "W"
rule: 4
registers: [0x0280, 0x02B8]
icon: "mdi:home-lightning-bolt"
# Load UPS output - The power of phase B is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "Load UPS L2 Power"
l: 2
hidden:
class: "power"
state_class: "measurement"
uom: "W"
rule: 4
registers: [0x0281, 0x02B9]
icon: "mdi:home-lightning-bolt"
# Load UPS output - The power of phase C is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "Load UPS L3 Power"
l: 3
hidden:
class: "power"
state_class: "measurement"
uom: "W"
rule: 4
registers: [0x0282, 0x02BA]
icon: "mdi:home-lightning-bolt"
# Load UPS output - The power is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "Load UPS Power"
l: 1
hidden:
class: "power"
state_class: "measurement"
uom: "W"
rule: 4
registers: [0x0283, 0x02BB]
icon: "mdi:home-lightning-bolt"
- group: Load
update_interval: 5
items:
# Load output - The voltage of phase A
- name: "Load L1 Voltage"
l: 1
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x0284]
# Load output - The voltage of phase B
- name: "Load L2 Voltage"
l: 2
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x0285]
# Load output - The voltage of phase C
- name: "Load L3 Voltage"
l: 3
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x0286]
# Load - The power of phase A is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "Load L1 Power"
l: 1
class: "power"
state_class: "measurement"
uom: "W"
rule: 4
registers: [0x028A, 0x0290]
# Load - The power of phase A is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "Load L2 Power"
l: 2
class: "power"
state_class: "measurement"
uom: "W"
rule: 4
registers: [0x028B, 0x0291]
# Load - The power of phase A is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "Load L3 Power"
l: 3
class: "power"
state_class: "measurement"
uom: "W"
rule: 4
registers: [0x028C, 0x0292]
# Load - The Power is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "Load Power"
l: 1
description: Combined power of all three phases
class: "power"
state_class: "measurement"
uom: "W"
rule: 4
registers: [0x028D, 0x0293]
- name: "Load Frequency"
l: 1
class: "frequency"
state_class: "measurement"
uom: "Hz"
scale: 0.01
rule: 1
registers: [0x028F]
- group: Generator/SmartLoad/Microinverter
update_interval: 5
items:
# Generator/SmartLoad/Microinverter - The voltage of phase A
- name: "Generator L1 Voltage"
name_lookup: "io_mode_select"
l: 1
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x0295]
# Generator/SmartLoad/Microinverter - The voltage of phase B
- name: "Generator L2 Voltage"
name_lookup: "io_mode_select"
l: 2
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x0296]
# Generator/SmartLoad/Microinverter - The voltage of phase C
- name: "Generator L3 Voltage"
name_lookup: "io_mode_select"
l: 3
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x0297]
# Generator - The power of phase A is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "Generator L1 Power"
name_lookup: "io_mode_select"
l: 1
class: "power"
state_class: "measurement"
uom: "W"
rule: 2
registers: [0x0298, 0x029C]
# Generator/SmartLoad/Microinverter - The power of phase A is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "Generator L2 Power"
name_lookup: "io_mode_select"
l: 2
class: "power"
state_class: "measurement"
uom: "W"
rule: 2
registers: [0x0299, 0x029D]
# Generator/SmartLoad/Microinverter - The power of phase A is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "Generator L3 Power"
name_lookup: "io_mode_select"
l: 3
class: "power"
state_class: "measurement"
uom: "W"
rule: 2
registers: [0x029A, 0x029E]
# Generator/SmartLoad/Microinverter - The Power is S16bit (low 16 bits) + S16bit (high 16 bits)
- name: "Generator Power"
name_lookup: "io_mode_select"
l: 1
description: Combined power of all three phases
class: "power"
state_class: "measurement"
uom: "W"
rule: 2
registers: [0x029B, 0x029F]
- group: PV
update_interval: 5
items:
# PV - The combined power of Input 1 & 2 & 3 & 4 (L:1W, H:10W)
- name: "PV Power"
alt: DC Power
mppt: 1
description: Combined power of all inputs
class: "power"
state_class: "measurement"
uom: "W"
rule: 1
digits: 0
scale: [1, 10]
sensors:
- registers: [0x02A0]
- registers: [0x02A1]
- registers: [0x02A2]
- registers: [0x02A3]
validation:
min: 0
max: [32000, 128000]
invalidate_all:
icon: "mdi:solar-power-variant"
# PV - The power of Input 1 (L:1W, H:10W)
- name: "PV1 Power"
alt: DC1 Power
mppt: 1
class: "power"
state_class: "measurement"
uom: "W"
scale: [1, 10]
rule: 1
registers: [0x02A0]
icon: "mdi:solar-power-variant"
# PV - The power of Input 2 (L:1W, H:10W)
- name: "PV2 Power"
alt: DC2 Power
mppt: 2
class: "power"
state_class: "measurement"
uom: "W"
scale: [1, 10]
rule: 1
registers: [0x02A1]
icon: "mdi:solar-power-variant"
# PV - The power of Input 3 (L:1W, H:10W)
- name: "PV3 Power"
alt: DC3 Power
mppt: 3
class: "power"
state_class: "measurement"
uom: "W"
scale: [1, 10]
rule: 1
registers: [0x02A2]
icon: "mdi:solar-power-variant"
# PV - The power of Input 4 (L:1W, H:10W)
- name: "PV4 Power"
alt: DC4 Power
mppt: 4
class: "power"
state_class: "measurement"
uom: "W"
scale: [1, 10]
rule: 1
registers: [0x02A3]
icon: "mdi:solar-power-variant"
- name: "PV1 Voltage"
alt: DC1 Voltage
mppt: 1
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x02A4]
icon: "mdi:solar-power-variant"
range:
min: 0
max: 65535
- name: "PV1 Current"
alt: DC1 Current
mppt: 1
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.1
rule: 1
registers: [0x02A5]
icon: "mdi:solar-power-variant"
range:
min: 0
max: 65535
- name: "PV2 Voltage"
alt: DC2 Voltage
mppt: 2
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x02A6]
icon: "mdi:solar-power-variant"
range:
min: 0
max: 65535
- name: "PV2 Current"
alt: DC2 Current
mppt: 2
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.1
rule: 1
registers: [0x02A7]
icon: "mdi:solar-power-variant"
range:
min: 0
max: 65535
- name: "PV3 Voltage"
alt: DC3 Voltage
mppt: 3
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x02A8]
icon: "mdi:solar-power-variant"
range:
min: 0
max: 65535
- name: "PV3 Current"
alt: DC3 Current
mppt: 3
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.1
rule: 1
registers: [0x02A9]
icon: "mdi:solar-power-variant"
range:
min: 0
max: 65535
- name: "PV4 Voltage"
alt: DC4 Voltage
mppt: 4
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x02AA]
icon: "mdi:solar-power-variant"
range:
min: 0
max: 65535
- name: "PV4 Current"
alt: DC4 Current
mppt: 4
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.1
rule: 1
registers: [0x02AB]
icon: "mdi:solar-power-variant"
range:
min: 0
max: 65535
- group: Battery 1
via_device: "inverter"
update_interval: 300
pack: 1
items:
- name: "Battery 1 Serial Number"
update_interval: 3600
attribute:
state_class: "measurement"
rule: 5
registers:
[0x2730, 0x2731, 0x2732, 0x2733, 0x2734, 0x2735, 0x2736, 0x2737]
- name: "Battery 1 Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x2738]
- name: "Battery 1 Current"
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.1
rule: 2
registers: [0x2739]
icon: "mdi:current-dc"
- name: "Battery 1 Max Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x273B]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 1 Min Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x273C]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 1 MOS Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x273D]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 1 Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x273A]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 1"
class: "battery"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x273F]
icon: "mdi:battery"
validation:
min: 0
max: 101
attributes:
[
"Battery 1 Serial Number",
"Battery 1 MOS",
"Battery 1 Software Version",
"Battery 1 Hardware Version",
]
- name: "Battery 1 SOH"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x2740]
icon: "mdi:battery-heart"
- name: "Battery 1 Capacity"
state_class: "measurement"
uom: "Ah"
rule: 1
scale: 0.1
registers: [0x2742]
icon: "mdi:battery"
- name: "Battery 1 Imbalance"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
sensors:
- registers: [0x2746]
- operator: subtract
registers: [0x2747]
- name: "Battery 1 Max Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x2746]
- name: "Battery 1 Min Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x2747]
- name: "Battery 1 Cycles"
state_class: "total_increasing"
rule: 1
registers: [0x2748]
icon: "mdi:battery-sync"
- name: "Battery 1 MOS"
attribute:
rule: 1
icon: "mdi:state-machine"
registers: [0x2749]
- name: "Battery 1 Alarm"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x274A, 0x274B]
icon: "mdi:battery-alert"
attributes: ["value"]
- name: "Battery 1 Fault"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x274C, 0x274D]
icon: "mdi:battery-alert-variant"
attributes: ["value"]
- name: "Battery 1 Software Version"
attribute:
rule: 7
delimiter: ""
registers: [0x274E]
- name: "Battery 1 Hardware Version"
attribute:
rule: 7
delimiter: ""
registers: [0x274F]
- group: Battery 2
via_device: "inverter"
update_interval: 300
pack: 2
items:
- name: "Battery 2 Serial Number"
update_interval: 3600
attribute:
state_class: "measurement"
rule: 5
registers:
[0x2756, 0x2757, 0x2758, 0x2759, 0x275A, 0x275B, 0x275C, 0x275D]
- name: "Battery 2 Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x275E]
- name: "Battery 2 Current"
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.1
rule: 2
registers: [0x275F]
icon: "mdi:current-dc"
- name: "Battery 2 Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2760]
range:
min: -99
max: 3000
validation:
min: 1
max: 99
- name: "Battery 2 Max Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2761]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 2 Min Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2762]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 2 MOS Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2763]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 2"
class: "battery"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x2765]
icon: "mdi:battery"
validation:
min: 0
max: 101
attributes:
[
"Battery 2 Serial Number",
"Battery 2 MOS",
"Battery 2 Software Version",
"Battery 2 Hardware Version",
]
- name: "Battery 2 SOH"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x2766]
icon: "mdi:battery-heart"
- name: "Battery 2 Capacity"
state_class: "measurement"
uom: "Ah"
rule: 1
scale: 0.1
registers: [0x2768]
icon: "mdi:battery"
- name: "Battery 2 Imbalance"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
sensors:
- registers: [0x276C]
- operator: subtract
registers: [0x276D]
- name: "Battery 2 Max Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x276C]
- name: "Battery 2 Min Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x276D]
- name: "Battery 2 Cycles"
state_class: "total_increasing"
rule: 1
registers: [0x276E]
icon: "mdi:battery-sync"
- name: "Battery 2 MOS"
attribute:
rule: 1
icon: "mdi:state-machine"
registers: [0x276F]
- name: "Battery 2 Alarm"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x2770, 0x2771]
icon: "mdi:battery-alert"
attributes: ["value"]
- name: "Battery 2 Fault"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x2772, 0x2773]
icon: "mdi:battery-alert-variant"
attributes: ["value"]
- name: "Battery 2 Software Version"
attribute:
rule: 7
delimiter: ""
registers: [0x2774]
- name: "Battery 2 Hardware Version"
attribute:
rule: 7
delimiter: ""
registers: [0x2775]
- group: Battery 3
via_device: "inverter"
update_interval: 300
pack: 3
items:
- name: "Battery 3 Serial Number"
update_interval: 3600
attribute:
state_class: "measurement"
rule: 5
registers:
[0x277C, 0x277D, 0x277E, 0x277F, 0x2780, 0x2781, 0x2782, 0x2783]
- name: "Battery 3 Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x2784]
- name: "Battery 3 Current"
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.1
rule: 2
registers: [0x2785]
icon: "mdi:current-dc"
- name: "Battery 3 Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2786]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 3 Max Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2787]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 3 Min Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2788]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 3 MOS Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2789]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 3"
class: "battery"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x278B]
icon: "mdi:battery"
validation:
min: 0
max: 101
attributes:
[
"Battery 3 Serial Number",
"Battery 3 MOS",
"Battery 3 Software Version",
"Battery 3 Hardware Version",
]
- name: "Battery 3 SOH"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x278C]
icon: "mdi:battery-heart"
- name: "Battery 3 Capacity"
state_class: "measurement"
uom: "Ah"
rule: 1
scale: 0.1
registers: [0x278E]
icon: "mdi:battery"
- name: "Battery 3 Imbalance"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
sensors:
- registers: [0x2792]
- operator: subtract
registers: [0x2793]
- name: "Battery 3 Max Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x2792]
- name: "Battery 3 Min Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x2793]
- name: "Battery 3 Cycles"
state_class: "total_increasing"
rule: 1
registers: [0x2794]
icon: "mdi:battery-sync"
- name: "Battery 3 MOS"
attribute:
rule: 1
icon: "mdi:state-machine"
registers: [0x2795]
- name: "Battery 3 Alarm"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x2796, 0x2797]
icon: "mdi:battery-alert"
attributes: ["value"]
- name: "Battery 3 Fault"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x2798, 0x2799]
icon: "mdi:battery-alert-variant"
attributes: ["value"]
- name: "Battery 3 Software Version"
attribute:
rule: 7
delimiter: ""
registers: [0x279A]
- name: "Battery 3 Hardware Version"
attribute:
rule: 7
delimiter: ""
registers: [0x279B]
- group: Battery 4
via_device: "inverter"
update_interval: 300
pack: 4
items:
- name: "Battery 4 Serial Number"
update_interval: 3600
attribute:
state_class: "measurement"
rule: 5
registers:
[0x27A2, 0x27A3, 0x27A4, 0x27A5, 0x27A6, 0x27A7, 0x27A8, 0x27A9]
- name: "Battery 4 Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x27AA]
- name: "Battery 4 Current"
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.1
rule: 2
registers: [0x27AB]
icon: "mdi:current-dc"
- name: "Battery 4 Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x27AC]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 4 Max Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x27AD]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 4 Min Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x27AE]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 4 MOS Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x27AF]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 4"
class: "battery"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x27B1]
icon: "mdi:battery"
validation:
min: 0
max: 101
attributes:
[
"Battery 4 Serial Number",
"Battery 4 MOS",
"Battery 4 Software Version",
"Battery 4 Hardware Version",
]
- name: "Battery 4 SOH"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x27B2]
icon: "mdi:battery-heart"
- name: "Battery 4 Capacity"
state_class: "measurement"
uom: "Ah"
rule: 1
scale: 0.1
registers: [0x27B4]
icon: "mdi:battery"
- name: "Battery 4 Imbalance"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
sensors:
- registers: [0x27B8]
- operator: subtract
registers: [0x27B9]
- name: "Battery 4 Max Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x27B8]
- name: "Battery 4 Min Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x27B9]
- name: "Battery 4 Cycles"
state_class: "total_increasing"
rule: 1
registers: [0x27BA]
icon: "mdi:battery-sync"
- name: "Battery 4 MOS"
attribute:
rule: 1
icon: "mdi:state-machine"
registers: [0x27BB]
- name: "Battery 4 Alarm"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x27BC, 0x27BD]
icon: "mdi:battery-alert"
attributes: ["value"]
- name: "Battery 4 Fault"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x27BE, 0x27BF]
icon: "mdi:battery-alert-variant"
attributes: ["value"]
- name: "Battery 4 Software Version"
attribute:
rule: 7
delimiter: ""
registers: [0x27C0]
- name: "Battery 4 Hardware Version"
attribute:
rule: 7
delimiter: ""
registers: [0x27C1]
- group: Battery 5
via_device: "inverter"
update_interval: 300
pack: 5
items:
- name: "Battery 5 Serial Number"
update_interval: 3600
attribute:
state_class: "measurement"
rule: 5
registers:
[0x27C8, 0x27C9, 0x27CA, 0x27CB, 0x27CC, 0x27CD, 0x27CE, 0x27CF]
- name: "Battery 5 Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x27D0]
- name: "Battery 5 Current"
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.1
rule: 2
registers: [0x27D1]
icon: "mdi:current-dc"
- name: "Battery 5 Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x27D2]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 5 Max Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x27D3]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 5 Min Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x27D4]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 5 MOS Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x27D5]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 5"
class: "battery"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x27D7]
icon: "mdi:battery"
validation:
min: 0
max: 101
attributes:
[
"Battery 5 Serial Number",
"Battery 5 MOS",
"Battery 5 Software Version",
"Battery 5 Hardware Version",
]
- name: "Battery 5 SOH"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x27D8]
icon: "mdi:battery-heart"
- name: "Battery 5 Capacity"
state_class: "measurement"
uom: "Ah"
rule: 1
scale: 0.1
registers: [0x27DA]
icon: "mdi:battery"
- name: "Battery 5 Imbalance"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
sensors:
- registers: [0x27DE]
- operator: subtract
registers: [0x27DF]
- name: "Battery 5 Max Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x27DE]
- name: "Battery 5 Min Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x27DF]
- name: "Battery 5 Cycles"
state_class: "total_increasing"
rule: 1
registers: [0x27E0]
icon: "mdi:battery-sync"
- name: "Battery 5 MOS"
attribute:
rule: 1
icon: "mdi:state-machine"
registers: [0x27E1]
- name: "Battery 5 Alarm"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x27E2, 0x27E3]
icon: "mdi:battery-alert"
attributes: ["value"]
- name: "Battery 5 Fault"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x27E4, 0x27E5]
icon: "mdi:battery-alert-variant"
attributes: ["value"]
- name: "Battery 5 Software Version"
attribute:
rule: 7
delimiter: ""
registers: [0x27E6]
- name: "Battery 5 Hardware Version"
attribute:
rule: 7
delimiter: ""
registers: [0x27E7]
- group: Battery 6
via_device: "inverter"
update_interval: 300
pack: 6
items:
- name: "Battery 6 Serial Number"
update_interval: 3600
attribute:
state_class: "measurement"
rule: 5
registers:
[0x27EE, 0x27EF, 0x27F0, 0x27F1, 0x27F2, 0x27F3, 0x27F4, 0x27F5]
- name: "Battery 6 Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x27F6]
- name: "Battery 6 Current"
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.1
rule: 2
registers: [0x27F7]
icon: "mdi:current-dc"
- name: "Battery 6 Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x27F8]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 6 Max Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x27F9]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 6 Min Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x27FA]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 6 MOS Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x27FB]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 6"
class: "battery"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x27FD]
icon: "mdi:battery"
validation:
min: 0
max: 101
attributes:
[
"Battery 6 Serial Number",
"Battery 6 MOS",
"Battery 6 Software Version",
"Battery 6 Hardware Version",
]
- name: "Battery 6 SOH"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x27FE]
icon: "mdi:battery-heart"
- name: "Battery 6 Capacity"
state_class: "measurement"
uom: "Ah"
rule: 1
scale: 0.1
registers: [0x2800]
icon: "mdi:battery"
- name: "Battery 6 Imbalance"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
sensors:
- registers: [0x2804]
- operator: subtract
registers: [0x2805]
- name: "Battery 6 Max Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x2804]
- name: "Battery 6 Min Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x2805]
- name: "Battery 6 Cycles"
state_class: "total_increasing"
rule: 1
registers: [0x2806]
icon: "mdi:battery-sync"
- name: "Battery 6 MOS"
attribute:
rule: 1
icon: "mdi:state-machine"
registers: [0x2807]
- name: "Battery 6 Alarm"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x2808, 0x2809]
icon: "mdi:battery-alert"
attributes: ["value"]
- name: "Battery 6 Fault"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x280A, 0x280B]
icon: "mdi:battery-alert-variant"
attributes: ["value"]
- name: "Battery 6 Software Version"
attribute:
rule: 7
delimiter: ""
registers: [0x280C]
- name: "Battery 6 Hardware Version"
attribute:
rule: 7
delimiter: ""
registers: [0x280D]
- group: Battery 7
via_device: "inverter"
update_interval: 300
pack: 7
items:
- name: "Battery 7 Serial Number"
update_interval: 3600
attribute:
state_class: "measurement"
rule: 5
registers:
[0x2814, 0x2815, 0x2816, 0x2817, 0x2818, 0x2819, 0x281A, 0x281B]
- name: "Battery 7 Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x281C]
- name: "Battery 7 Current"
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.1
rule: 2
registers: [0x281D]
icon: "mdi:current-dc"
- name: "Battery 7 Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x281E]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 7 Max Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x281F]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 7 Min Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2820]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 7 MOS Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2821]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 7"
class: "battery"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x2823]
icon: "mdi:battery"
validation:
min: 0
max: 101
attributes:
[
"Battery 7 Serial Number",
"Battery 7 MOS",
"Battery 7 Software Version",
"Battery 7 Hardware Version",
]
- name: "Battery 7 SOH"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x2824]
icon: "mdi:battery-heart"
- name: "Battery 7 Capacity"
state_class: "measurement"
uom: "Ah"
rule: 1
scale: 0.1
registers: [0x2826]
icon: "mdi:battery"
- name: "Battery 7 Imbalance"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
sensors:
- registers: [0x282A]
- operator: subtract
registers: [0x282B]
- name: "Battery 7 Max Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x282A]
- name: "Battery 7 Min Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x282B]
- name: "Battery 7 Cycles"
state_class: "total_increasing"
rule: 1
registers: [0x282C]
icon: "mdi:battery-sync"
- name: "Battery 7 MOS"
attribute:
rule: 1
icon: "mdi:state-machine"
registers: [0x282D]
- name: "Battery 7 Alarm"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x282E, 0x282F]
icon: "mdi:battery-alert"
attributes: ["value"]
- name: "Battery 7 Fault"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x2830, 0x2831]
icon: "mdi:battery-alert-variant"
attributes: ["value"]
- name: "Battery 7 Software Version"
attribute:
rule: 7
delimiter: ""
registers: [0x2832]
- name: "Battery 7 Hardware Version"
attribute:
rule: 7
delimiter: ""
registers: [0x2833]
- group: Battery 8
via_device: "inverter"
update_interval: 300
pack: 8
items:
- name: "Battery 8 Serial Number"
update_interval: 3600
attribute:
state_class: "measurement"
rule: 5
registers:
[0x283A, 0x283B, 0x283C, 0x283D, 0x283E, 0x283F, 0x2840, 0x2841]
- name: "Battery 8 Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x2842]
- name: "Battery 8 Current"
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.1
rule: 2
registers: [0x2843]
icon: "mdi:current-dc"
- name: "Battery 8 Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2844]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 8 Max Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2845]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 8 Min Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2846]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 8 MOS Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2847]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 8"
class: "battery"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x2849]
icon: "mdi:battery"
validation:
min: 0
max: 101
attributes:
[
"Battery 8 Serial Number",
"Battery 8 MOS",
"Battery 8 Software Version",
"Battery 8 Hardware Version",
]
- name: "Battery 8 SOH"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x284A]
icon: "mdi:battery-heart"
- name: "Battery 8 Capacity"
state_class: "measurement"
uom: "Ah"
rule: 1
scale: 0.1
registers: [0x284C]
icon: "mdi:battery"
- name: "Battery 8 Imbalance"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
sensors:
- registers: [0x2850]
- operator: subtract
registers: [0x2851]
- name: "Battery 8 Max Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x2850]
- name: "Battery 8 Min Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x2851]
- name: "Battery 8 Cycles"
state_class: "total_increasing"
rule: 1
registers: [0x2852]
icon: "mdi:battery-sync"
- name: "Battery 8 MOS"
attribute:
rule: 1
icon: "mdi:state-machine"
registers: [0x2853]
- name: "Battery 8 Alarm"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x2854, 0x2855]
icon: "mdi:battery-alert"
attributes: ["value"]
- name: "Battery 8 Fault"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x2856, 0x2857]
icon: "mdi:battery-alert-variant"
attributes: ["value"]
- name: "Battery 8 Software Version"
attribute:
rule: 7
delimiter: ""
registers: [0x2858]
- name: "Battery 8 Hardware Version"
attribute:
rule: 7
delimiter: ""
registers: [0x2859]
- group: Battery 9
via_device: "inverter"
update_interval: 300
pack: 9
items:
- name: "Battery 9 Serial Number"
update_interval: 3600
attribute:
state_class: "measurement"
rule: 5
registers:
[0x2860, 0x2861, 0x2862, 0x2863, 0x2864, 0x2865, 0x2866, 0x2867]
- name: "Battery 9 Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x2868]
- name: "Battery 9 Current"
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.1
rule: 2
registers: [0x2869]
icon: "mdi:current-dc"
- name: "Battery 9 Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x286A]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 9 Max Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x286B]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 9 Min Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x286C]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 9 MOS Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x286D]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 9"
class: "battery"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x286F]
icon: "mdi:battery"
validation:
min: 0
max: 101
attributes:
[
"Battery 9 Serial Number",
"Battery 9 MOS",
"Battery 9 Software Version",
"Battery 9 Hardware Version",
]
- name: "Battery 9 SOH"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x2870]
icon: "mdi:battery-heart"
- name: "Battery 9 Capacity"
state_class: "measurement"
uom: "Ah"
rule: 1
scale: 0.1
registers: [0x2872]
icon: "mdi:battery"
- name: "Battery 9 Imbalance"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
sensors:
- registers: [0x2876]
- operator: subtract
registers: [0x2877]
- name: "Battery 9 Max Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x2876]
- name: "Battery 9 Min Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x2877]
- name: "Battery 9 Cycles"
state_class: "total_increasing"
rule: 1
registers: [0x2878]
icon: "mdi:battery-sync"
- name: "Battery 9 MOS"
attribute:
rule: 1
icon: "mdi:state-machine"
registers: [0x2879]
- name: "Battery 9 Alarm"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x287A, 0x287B]
icon: "mdi:battery-alert"
attributes: ["value"]
- name: "Battery 9 Fault"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x287C, 0x287D]
icon: "mdi:battery-alert-variant"
attributes: ["value"]
- name: "Battery 9 Software Version"
attribute:
rule: 7
delimiter: ""
registers: [0x287E]
- name: "Battery 9 Hardware Version"
attribute:
rule: 7
delimiter: ""
registers: [0x287F]
- group: Battery 10
via_device: "inverter"
update_interval: 300
pack: 10
items:
- name: "Battery 10 Serial Number"
update_interval: 3600
attribute:
state_class: "measurement"
rule: 5
registers:
[0x2886, 0x2887, 0x2888, 0x2889, 0x288A, 0x288B, 0x288C, 0x288D]
- name: "Battery 10 Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x288E]
- name: "Battery 10 Current"
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.1
rule: 2
registers: [0x288F]
icon: "mdi:current-dc"
- name: "Battery 10 Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2890]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 10 Max Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2891]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 10 Min Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2892]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 10 MOS Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2893]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 10"
class: "battery"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x2895]
icon: "mdi:battery"
validation:
min: 0
max: 101
attributes:
[
"Battery 10 Serial Number",
"Battery 10 MOS",
"Battery 10 Software Version",
"Battery 10 Hardware Version",
]
- name: "Battery 10 SOH"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x2896]
icon: "mdi:battery-heart"
- name: "Battery 10 Capacity"
state_class: "measurement"
uom: "Ah"
rule: 1
scale: 0.1
registers: [0x2898]
icon: "mdi:battery"
- name: "Battery 10 Imbalance"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
sensors:
- registers: [0x289C]
- operator: subtract
registers: [0x289D]
- name: "Battery 10 Max Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x289C]
- name: "Battery 10 Min Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x289D]
- name: "Battery 10 Cycles"
state_class: "total_increasing"
rule: 1
registers: [0x289E]
icon: "mdi:battery-sync"
- name: "Battery 10 MOS"
attribute:
rule: 1
icon: "mdi:state-machine"
registers: [0x289F]
- name: "Battery 10 Alarm"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x28A0, 0x28A1]
icon: "mdi:battery-alert"
attributes: ["value"]
- name: "Battery 10 Fault"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x28A2, 0x28A3]
icon: "mdi:battery-alert-variant"
attributes: ["value"]
- name: "Battery 10 Software Version"
attribute:
rule: 7
delimiter: ""
registers: [0x28A4]
- name: "Battery 10 Hardware Version"
attribute:
rule: 7
delimiter: ""
registers: [0x28A5]
- group: Battery 11
via_device: "inverter"
update_interval: 300
pack: 11
items:
- name: "Battery 11 Serial Number"
update_interval: 3600
attribute:
state_class: "measurement"
rule: 5
registers:
[0x28AC, 0x28AD, 0x28AE, 0x28AF, 0x28B0, 0x28B1, 0x28B2, 0x28B3]
- name: "Battery 11 Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x28B4]
- name: "Battery 11 Current"
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.1
rule: 2
registers: [0x28B5]
icon: "mdi:current-dc"
- name: "Battery 11 Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x28B6]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 11 Max Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x28B7]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 11 Min Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x28B8]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 11 MOS Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x28B9]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 11"
class: "battery"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x28BB]
icon: "mdi:battery"
validation:
min: 0
max: 101
attributes:
[
"Battery 11 Serial Number",
"Battery 11 MOS",
"Battery 11 Software Version",
"Battery 11 Hardware Version",
]
- name: "Battery 11 SOH"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x28BC]
icon: "mdi:battery-heart"
- name: "Battery 11 Capacity"
state_class: "measurement"
uom: "Ah"
rule: 1
scale: 0.1
registers: [0x28BE]
icon: "mdi:battery"
- name: "Battery 11 Imbalance"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
sensors:
- registers: [0x28C2]
- operator: subtract
registers: [0x28C3]
- name: "Battery 11 Max Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x28C2]
- name: "Battery 11 Min Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x28C3]
- name: "Battery 11 Cycles"
state_class: "total_increasing"
rule: 1
registers: [0x28C4]
icon: "mdi:battery-sync"
- name: "Battery 11 MOS"
attribute:
rule: 1
icon: "mdi:state-machine"
registers: [0x28C5]
- name: "Battery 11 Alarm"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x28C6, 0x28C7]
icon: "mdi:battery-alert"
attributes: ["value"]
- name: "Battery 11 Fault"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x28C8, 0x28C9]
icon: "mdi:battery-alert-variant"
attributes: ["value"]
- name: "Battery 11 Software Version"
attribute:
rule: 7
delimiter: ""
registers: [0x28CA]
- name: "Battery 11 Hardware Version"
attribute:
rule: 7
delimiter: ""
registers: [0x28CB]
- group: Battery 12
via_device: "inverter"
update_interval: 300
pack: 12
items:
- name: "Battery 12 Serial Number"
update_interval: 3600
attribute:
state_class: "measurement"
rule: 5
registers:
[0x28D2, 0x28D3, 0x28D4, 0x28D5, 0x28D6, 0x28D7, 0x28D8, 0x28D9]
- name: "Battery 12 Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x28DA]
- name: "Battery 12 Current"
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.1
rule: 2
registers: [0x28DB]
icon: "mdi:current-dc"
- name: "Battery 12 Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x28DC]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 12 Max Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x28DD]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 12 Min Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x28DE]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 12 MOS Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x28DF]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 12"
class: "battery"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x28E1]
icon: "mdi:battery"
validation:
min: 0
max: 101
attributes:
[
"Battery 12 Serial Number",
"Battery 12 MOS",
"Battery 12 Software Version",
"Battery 12 Hardware Version",
]
- name: "Battery 12 SOH"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x28E2]
icon: "mdi:battery-heart"
- name: "Battery 12 Capacity"
state_class: "measurement"
uom: "Ah"
rule: 1
scale: 0.1
registers: [0x28E4]
icon: "mdi:battery"
- name: "Battery 12 Imbalance"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
sensors:
- registers: [0x28E8]
- operator: subtract
registers: [0x28E9]
- name: "Battery 12 Max Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x28E8]
- name: "Battery 12 Min Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x28E9]
- name: "Battery 12 Cycles"
state_class: "total_increasing"
rule: 1
registers: [0x28EA]
icon: "mdi:battery-sync"
- name: "Battery 12 MOS"
attribute:
rule: 1
icon: "mdi:state-machine"
registers: [0x28EB]
- name: "Battery 12 Alarm"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x28EC, 0x28ED]
icon: "mdi:battery-alert"
attributes: ["value"]
- name: "Battery 12 Fault"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x28EE, 0x28EF]
icon: "mdi:battery-alert-variant"
attributes: ["value"]
- name: "Battery 12 Software Version"
attribute:
rule: 7
delimiter: ""
registers: [0x28F0]
- name: "Battery 12 Hardware Version"
attribute:
rule: 7
delimiter: ""
registers: [0x28F1]
- group: Battery 13
via_device: "inverter"
update_interval: 300
pack: 13
items:
- name: "Battery 13 Serial Number"
update_interval: 3600
attribute:
state_class: "measurement"
rule: 5
registers:
[0x28F8, 0x28F9, 0x28FA, 0x28FB, 0x28FC, 0x28FD, 0x28FE, 0x28FF]
- name: "Battery 13 Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x2900]
- name: "Battery 13 Current"
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.1
rule: 2
registers: [0x2901]
icon: "mdi:current-dc"
- name: "Battery 13 Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2902]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 13 Max Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2903]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 13 Min Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2904]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 13 MOS Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2905]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 13"
class: "battery"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x2907]
icon: "mdi:battery"
validation:
min: 0
max: 101
attributes:
[
"Battery 13 Serial Number",
"Battery 13 MOS",
"Battery 13 Software Version",
"Battery 13 Hardware Version",
]
- name: "Battery 13 SOH"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x2908]
icon: "mdi:battery-heart"
- name: "Battery 13 Capacity"
state_class: "measurement"
uom: "Ah"
rule: 1
scale: 0.1
registers: [0x290A]
icon: "mdi:battery"
- name: "Battery 13 Imbalance"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
sensors:
- registers: [0x290E]
- operator: subtract
registers: [0x290F]
- name: "Battery 13 Max Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x290E]
- name: "Battery 13 Min Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x290F]
- name: "Battery 13 Cycles"
state_class: "total_increasing"
rule: 1
registers: [0x2910]
icon: "mdi:battery-sync"
- name: "Battery 13 MOS"
attribute:
rule: 1
icon: "mdi:state-machine"
registers: [0x2911]
- name: "Battery 13 Alarm"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x2912, 0x2913]
icon: "mdi:battery-alert"
attributes: ["value"]
- name: "Battery 13 Fault"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x2914, 0x2915]
icon: "mdi:battery-alert-variant"
attributes: ["value"]
- name: "Battery 13 Software Version"
attribute:
rule: 7
delimiter: ""
registers: [0x2916]
- name: "Battery 13 Hardware Version"
attribute:
rule: 7
delimiter: ""
registers: [0x2917]
- group: Battery 14
via_device: "inverter"
update_interval: 300
pack: 14
items:
- name: "Battery 14 Serial Number"
update_interval: 3600
attribute:
state_class: "measurement"
rule: 5
registers:
[0x291E, 0x291F, 0x2920, 0x2921, 0x2922, 0x2923, 0x2924, 0x2925]
- name: "Battery 14 Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x2926]
- name: "Battery 14 Current"
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.1
rule: 2
registers: [0x2927]
icon: "mdi:current-dc"
- name: "Battery 14 Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2928]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 14 Max Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2929]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 14 Min Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x292A]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 14 MOS Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x292B]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 14"
class: "battery"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x292D]
icon: "mdi:battery"
validation:
min: 0
max: 101
attributes:
[
"Battery 14 Serial Number",
"Battery 14 MOS",
"Battery 14 Software Version",
"Battery 14 Hardware Version",
]
- name: "Battery 14 SOH"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x292E]
icon: "mdi:battery-heart"
- name: "Battery 14 Capacity"
state_class: "measurement"
uom: "Ah"
rule: 1
scale: 0.1
registers: [0x2930]
icon: "mdi:battery"
- name: "Battery 14 Imbalance"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
sensors:
- registers: [0x2934]
- operator: subtract
registers: [0x2935]
- name: "Battery 14 Max Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x2934]
- name: "Battery 14 Min Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x2935]
- name: "Battery 14 Cycles"
state_class: "total_increasing"
rule: 1
registers: [0x2936]
icon: "mdi:battery-sync"
- name: "Battery 14 MOS"
attribute:
rule: 1
icon: "mdi:state-machine"
registers: [0x2937]
- name: "Battery 14 Alarm"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x2938, 0x2939]
icon: "mdi:battery-alert"
attributes: ["value"]
- name: "Battery 14 Fault"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x293A, 0x293B]
icon: "mdi:battery-alert-variant"
attributes: ["value"]
- name: "Battery 14 Software Version"
attribute:
rule: 7
delimiter: ""
registers: [0x293C]
- name: "Battery 14 Hardware Version"
attribute:
rule: 7
delimiter: ""
registers: [0x293D]
- group: Battery 15
via_device: "inverter"
update_interval: 300
pack: 15
items:
- name: "Battery 15 Serial Number"
update_interval: 3600
attribute:
state_class: "measurement"
rule: 5
registers:
[0x2944, 0x2945, 0x2946, 0x2947, 0x2948, 0x2949, 0x294A, 0x294B]
- name: "Battery 15 Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x294C]
- name: "Battery 15 Current"
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.1
rule: 2
registers: [0x294D]
icon: "mdi:current-dc"
- name: "Battery 15 Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x294E]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 15 Max Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x294F]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 15 Min Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2950]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 15 MOS Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2951]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 15"
class: "battery"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x2953]
icon: "mdi:battery"
validation:
min: 0
max: 101
attributes:
[
"Battery 15 Serial Number",
"Battery 15 MOS",
"Battery 15 Software Version",
"Battery 15 Hardware Version",
]
- name: "Battery 15 SOH"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x2954]
icon: "mdi:battery-heart"
- name: "Battery 15 Capacity"
state_class: "measurement"
uom: "Ah"
rule: 1
scale: 0.1
registers: [0x2956]
icon: "mdi:battery"
- name: "Battery 15 Imbalance"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
sensors:
- registers: [0x295A]
- operator: subtract
registers: [0x295B]
- name: "Battery 15 Max Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x295A]
- name: "Battery 15 Min Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x295B]
- name: "Battery 15 Cycles"
state_class: "total_increasing"
rule: 1
registers: [0x295C]
icon: "mdi:battery-sync"
- name: "Battery 15 MOS"
attribute:
rule: 1
icon: "mdi:state-machine"
registers: [0x295D]
- name: "Battery 15 Alarm"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x295E, 0x295F]
icon: "mdi:battery-alert"
attributes: ["value"]
- name: "Battery 15 Fault"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x2960, 0x2961]
icon: "mdi:battery-alert-variant"
attributes: ["value"]
- name: "Battery 15 Software Version"
attribute:
rule: 7
delimiter: ""
registers: [0x2962]
- name: "Battery 15 Hardware Version"
attribute:
rule: 7
delimiter: ""
registers: [0x2963]
- group: Battery 16
via_device: "inverter"
update_interval: 300
pack: 16
items:
- name: "Battery 16 Serial Number"
update_interval: 3600
attribute:
state_class: "measurement"
rule: 5
registers:
[0x296A, 0x296B, 0x296C, 0x296D, 0x296E, 0x296F, 0x2970, 0x2971]
- name: "Battery 16 Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x2972]
- name: "Battery 16 Current"
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.1
rule: 2
registers: [0x2973]
icon: "mdi:current-dc"
- name: "Battery 16 Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2974]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 16 Max Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2975]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 16 Min Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2976]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 16 MOS Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2977]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 16"
class: "battery"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x2979]
icon: "mdi:battery"
validation:
min: 0
max: 101
attributes:
[
"Battery 16 Serial Number",
"Battery 16 MOS",
"Battery 16 Software Version",
"Battery 16 Hardware Version",
]
- name: "Battery 16 SOH"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x297A]
icon: "mdi:battery-heart"
- name: "Battery 16 Capacity"
state_class: "measurement"
uom: "Ah"
rule: 1
scale: 0.1
registers: [0x297C]
icon: "mdi:battery"
- name: "Battery 16 Imbalance"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
sensors:
- registers: [0x2980]
- operator: subtract
registers: [0x2981]
- name: "Battery 16 Max Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x2980]
- name: "Battery 16 Min Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x2981]
- name: "Battery 16 Cycles"
state_class: "total_increasing"
rule: 1
registers: [0x2982]
icon: "mdi:battery-sync"
- name: "Battery 16 MOS"
attribute:
rule: 1
icon: "mdi:state-machine"
registers: [0x2983]
- name: "Battery 16 Alarm"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x2984, 0x2985]
icon: "mdi:battery-alert"
attributes: ["value"]
- name: "Battery 16 Fault"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x2986, 0x2987]
icon: "mdi:battery-alert-variant"
attributes: ["value"]
- name: "Battery 16 Software Version"
attribute:
rule: 7
delimiter: ""
registers: [0x2988]
- name: "Battery 16 Hardware Version"
attribute:
rule: 7
delimiter: ""
registers: [0x2989]
- group: Battery 17
via_device: "inverter"
update_interval: 300
pack: 17
items:
- name: "Battery 17 Serial Number"
update_interval: 3600
attribute:
state_class: "measurement"
rule: 5
registers:
[0x2990, 0x2991, 0x2992, 0x2993, 0x2994, 0x2995, 0x2996, 0x2997]
- name: "Battery 17 Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x2998]
- name: "Battery 17 Current"
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.1
rule: 2
registers: [0x2999]
icon: "mdi:current-dc"
- name: "Battery 17 Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x299A]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 17 Max Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x299B]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 17 Min Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x299C]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 17 MOS Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x299D]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 17"
class: "battery"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x299F]
icon: "mdi:battery"
validation:
min: 0
max: 101
attributes:
[
"Battery 17 Serial Number",
"Battery 17 MOS",
"Battery 17 Software Version",
"Battery 17 Hardware Version",
]
- name: "Battery 17 SOH"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x29A0]
icon: "mdi:battery-heart"
- name: "Battery 17 Capacity"
state_class: "measurement"
uom: "Ah"
rule: 1
scale: 0.1
registers: [0x29A2]
icon: "mdi:battery"
- name: "Battery 17 Imbalance"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
sensors:
- registers: [0x29A6]
- operator: subtract
registers: [0x29A7]
- name: "Battery 17 Max Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x29A6]
- name: "Battery 17 Min Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x29A7]
- name: "Battery 17 Cycles"
state_class: "total_increasing"
rule: 1
registers: [0x29A8]
icon: "mdi:battery-sync"
- name: "Battery 17 MOS"
attribute:
rule: 1
icon: "mdi:state-machine"
registers: [0x29A9]
- name: "Battery 17 Alarm"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x29AA, 0x29AB]
icon: "mdi:battery-alert"
attributes: ["value"]
- name: "Battery 17 Fault"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x29AC, 0x29AD]
icon: "mdi:battery-alert-variant"
attributes: ["value"]
- name: "Battery 17 Software Version"
attribute:
rule: 7
delimiter: ""
registers: [0x29AE]
- name: "Battery 17 Hardware Version"
attribute:
rule: 7
delimiter: ""
registers: [0x29AF]
- group: Battery 18
via_device: "inverter"
update_interval: 300
pack: 18
items:
- name: "Battery 18 Serial Number"
update_interval: 3600
attribute:
state_class: "measurement"
rule: 5
registers:
[0x29B6, 0x29B7, 0x29B8, 0x29B9, 0x29BA, 0x29BB, 0x29BC, 0x29BD]
- name: "Battery 18 Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x29BE]
- name: "Battery 18 Current"
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.1
rule: 2
registers: [0x29BF]
icon: "mdi:current-dc"
- name: "Battery 18 Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x29C0]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 18 Max Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x29C1]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 18 Min Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x29C2]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 18 MOS Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x29C3]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 18"
class: "battery"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x29C5]
icon: "mdi:battery"
validation:
min: 0
max: 101
attributes:
[
"Battery 18 Serial Number",
"Battery 18 MOS",
"Battery 18 Software Version",
"Battery 18 Hardware Version",
]
- name: "Battery 18 SOH"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x29C6]
icon: "mdi:battery-heart"
- name: "Battery 18 Capacity"
state_class: "measurement"
uom: "Ah"
rule: 1
scale: 0.1
registers: [0x29C8]
icon: "mdi:battery"
- name: "Battery 18 Imbalance"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
sensors:
- registers: [0x29CC]
- operator: subtract
registers: [0x29CD]
- name: "Battery 18 Max Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x29CC]
- name: "Battery 18 Min Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x29CD]
- name: "Battery 18 Cycles"
state_class: "total_increasing"
rule: 1
registers: [0x29CE]
icon: "mdi:battery-sync"
- name: "Battery 18 MOS"
attribute:
rule: 1
icon: "mdi:state-machine"
registers: [0x29CF]
- name: "Battery 18 Alarm"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x29D0, 0x29D1]
icon: "mdi:battery-alert"
attributes: ["value"]
- name: "Battery 18 Fault"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x29D2, 0x29D3]
icon: "mdi:battery-alert-variant"
attributes: ["value"]
- name: "Battery 18 Software Version"
attribute:
rule: 7
delimiter: ""
registers: [0x29D4]
- name: "Battery 18 Hardware Version"
attribute:
rule: 7
delimiter: ""
registers: [0x29D5]
- group: Battery 19
via_device: "inverter"
update_interval: 300
pack: 19
items:
- name: "Battery 19 Serial Number"
update_interval: 3600
attribute:
state_class: "measurement"
rule: 5
registers:
[0x29DC, 0x29DD, 0x29DE, 0x29DF, 0x29E0, 0x29E1, 0x29E2, 0x29E3]
- name: "Battery 19 Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x29E4]
- name: "Battery 19 Current"
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.1
rule: 2
registers: [0x29E5]
icon: "mdi:current-dc"
- name: "Battery 19 Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x29E6]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 19 Max Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x29E7]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 19 Min Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x29E8]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 19 MOS Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x29E9]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 19"
class: "battery"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x29EB]
icon: "mdi:battery"
validation:
min: 0
max: 101
attributes:
[
"Battery 19 Serial Number",
"Battery 19 MOS",
"Battery 19 Software Version",
"Battery 19 Hardware Version",
]
- name: "Battery 19 SOH"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x29EC]
icon: "mdi:battery-heart"
- name: "Battery 19 Capacity"
state_class: "measurement"
uom: "Ah"
rule: 1
scale: 0.1
registers: [0x29EE]
icon: "mdi:battery"
- name: "Battery 19 Imbalance"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
sensors:
- registers: [0x29F2]
- operator: subtract
registers: [0x29F3]
- name: "Battery 19 Max Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x29F2]
- name: "Battery 19 Min Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x29F3]
- name: "Battery 19 Cycles"
state_class: "total_increasing"
rule: 1
registers: [0x29F4]
icon: "mdi:battery-sync"
- name: "Battery 19 MOS"
attribute:
rule: 1
icon: "mdi:state-machine"
registers: [0x29F5]
- name: "Battery 19 Alarm"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x29F6, 0x29F7]
icon: "mdi:battery-alert"
attributes: ["value"]
- name: "Battery 19 Fault"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x29F8, 0x29F9]
icon: "mdi:battery-alert-variant"
attributes: ["value"]
- name: "Battery 19 Software Version"
attribute:
rule: 7
delimiter: ""
registers: [0x29FA]
- name: "Battery 19 Hardware Version"
attribute:
rule: 7
delimiter: ""
registers: [0x29FB]
- group: Battery 20
via_device: "inverter"
update_interval: 300
pack: 20
items:
- name: "Battery 20 Serial Number"
update_interval: 3600
attribute:
state_class: "measurement"
rule: 5
registers:
[0x2A02, 0x2A03, 0x2A04, 0x2A05, 0x2A06, 0x2A07, 0x2A08, 0x2A09]
- name: "Battery 20 Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.1
rule: 1
registers: [0x2A0A]
- name: "Battery 20 Current"
class: "current"
state_class: "measurement"
uom: "A"
scale: 0.1
rule: 2
registers: [0x2A0B]
icon: "mdi:current-dc"
- name: "Battery 20 Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2A0C]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 20 Max Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2A0D]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 20 Min Cell Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2A0E]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 20 MOS Temperature"
class: "temperature"
state_class: "measurement"
uom: "°C"
scale: 0.1
rule: 1
offset: 1000
registers: [0x2A0F]
range:
min: 0
max: 3000
validation:
min: -99
max: 99
- name: "Battery 20"
class: "battery"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x2A11]
icon: "mdi:battery"
validation:
min: 0
max: 101
attributes:
[
"Battery 20 Serial Number",
"Battery 20 MOS",
"Battery 20 Software Version",
"Battery 20 Hardware Version",
]
- name: "Battery 20 SOH"
state_class: "measurement"
uom: "%"
scale: 0.1
rule: 1
registers: [0x2A12]
icon: "mdi:battery-heart"
- name: "Battery 20 Capacity"
state_class: "measurement"
uom: "Ah"
rule: 1
scale: 0.1
registers: [0x2A14]
icon: "mdi:battery"
- name: "Battery 20 Imbalance"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
sensors:
- registers: [0x2A18]
- operator: subtract
registers: [0x2A19]
- name: "Battery 20 Max Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x2A18]
- name: "Battery 20 Min Cell Voltage"
class: "voltage"
state_class: "measurement"
uom: "V"
scale: 0.001
rule: 1
registers: [0x2A19]
- name: "Battery 20 Cycles"
state_class: "total_increasing"
rule: 1
registers: [0x2A1A]
- name: "Battery 20 MOS"
attribute:
rule: 1
icon: "mdi:state-machine"
registers: [0x2A1B]
- name: "Battery 20 Alarm"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x2A1C, 0x2A1D]
icon: "mdi:battery-alert"
attributes: ["value"]
- name: "Battery 20 Fault"
platform: binary_sensor
class: "problem"
rule: 1
registers: [0x2A1E, 0x2A1F]
icon: "mdi:battery-alert-variant"
attributes: ["value"]
- name: "Battery 20 Software Version"
attribute:
rule: 7
delimiter: ""
registers: [0x2A20]
- name: "Battery 20 Hardware Version"
attribute:
rule: 7
delimiter: ""
registers: [0x2A21]
Sign up for free to join this conversation on GitHub. Already have an account? Sign in to comment